Intended to maintain continuous and equal condensate levels in connection lines transferring the pressure difference from a bladder to pressure difference gauges, at the change of vapour flow rate.
Intended to maintain continuous and equal condensate levels in connection lines transferring the pressure difference from a bladder to pressure difference gauges, at the change of vapour flow rate.
Использование | Pressure |
Conventional symbol | Nominal pressure, MPa | Version | Material | Weight, kg, not more |
---|---|---|---|---|
СК-4-1-А | 4 | 1 | Steel 20 | 3,1 |
СК-4-1-Б | Steel 12Х18Н10Т | |||
СК-10-1-А | 10 | Steel 20 | 4,0 | |
СК-10-1-Б | Steel 12Х18Н10Т | |||
СК-25-А | 25 | - | Steel 20 | 2,1 |
СК-25-Б | Steel 12Х18Н10Т | |||
СК-40-А | 40 | Steel 20 | ||
СК-40-Б | Steel 12Х18Н10Т |
Operating medium temperature, ºС | Permissible operating pressure, MPa | |||||
---|---|---|---|---|---|---|
Steel 20 | Steel 12Х18Н10Т | |||||
20* | 4 | 6,3 | 10 | 25 | 40 | |
200 | 200 | 4 | 6,3 | 10 | 25 | 40 |
250 | 325 | 3,5 | 5,4 | 9 | 23 | 35 |
300 | 400 | 3 | 4,8 | 7,5 | 19 | 30 |
350 | 480 | 2,6 | 4 | 6,6 | 17 | 26 |
* — at the temperature 20 ºС a permissible operating pressure is equal to a nominal one
Body frame part materials | Code of materials in the vessel conventional designation |
---|---|
Steel 20 GOST 1050 | А |
Steel 12Х18Н10Т GOST 5632 | Б |
Parameter | Value |
---|---|
Warranty operating life, months | 36 months since the commissioning date but no more than 42 months since the date of manufacture |
Name | Number |
---|---|
Vessel | 1 |
Data Sheet | 1 |
Сосуд конденсационный | СК-25-Б |
---|---|
1 | 2 |